Dry Riser Testing & Servicing frequency
Servicing Requirements for Dry Risers
Dry Riser Maintenance frequency:
- Dry risers are required to have a 6 monthly visual check,
- Every 12 months a water test should be carried out to 12 bar for 15 minutes.
This is a legal requirement dictated by BS9990:2015 which is the British Standard that details requirements for dry riser testing and maintenance in the UK.
The 6 monthly visual check which is primarily an anti theft or anti vandalism check. This should be carried out by a competent person with the records stored in a safe place, should they be required by the local authorities. The annual water test should be carried out to 12 bar for 15 minutes. A professional company with the correct equipment, processes and H&S records should be utilised.
Dry Riser testing frequency and dry riser maintenance requirements: Dry Risers Direct know the answer and are here to help.